Permit: TC-RES-0626-03365

Parcel: 135021840


Addresses:

6442 E CALLE BOOTIS

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Date Description Inspector Results Comments
08/31/2026 COT - RSBU - Roof Nailing  Re-inspection required Improper installation of SDWC truss screws, is it designed to be installed to top plate not to the roof sheating. Please follow diagram in plans for proper install. You may use H2.5s or correct screw installation. No ladder provided for roof nail inspection.
09/01/2026 COT - RSBU - Roof Nailing  Re-inspection required Improper installation of SDWC truss screws, is it designed to be installed to top plate not to the roof sheating. Please follow diagram in plans for proper install. You may use H2.5s or correct screw installation. No ladder provided for roof nail inspection.

9.1.26
- 1/2 shiplap siding was used for roof sheating, contractor submitted 5/8 T1-11 on the approved plans.
- over penetrated fasteners on sheating.
09/02/2026 COT - RSBU - Roof Nailing  Passed