Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 08/13/2026 |
COT - RSME - Mechanical Final |
|
Re-inspection required |
8-13-26: replace double pole 60 amp breaker to a 40amp at main panel, add a support to exhaust, and correct refrigerant copper line leak at unit in attic. |
| 08/20/2026 |
COT - RSME - Mechanical Final |
|
Passed |
8-20-26 All corrections have been made |