Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 05/28/2025 |
COT - RSME - Mechanical Final |
|
Re-inspection required |
5-28-25, missing cooktop and anti tip device, missing address identification sign on residence, cut cleanouts to grade, gas meter must be installed, hammer arrestors required at washer/dryer, 90 degree elbows required on exterior plastic, paint all exterior pvc, insulate copper hose bib and wrap with 10 mil tap, 2 clamps are required for electrical risers, vacuum breakers required on hose bibs, gfci receptacles are required on kitchen and bathrooms, a ledger board with a future light box was installed on home and is not per approved plans-submit an RFI or remove altogether, provide plans to verify thermostat height. If home was designed as an inclusive home then height shall be at 42" o.c... |
| 05/30/2025 |
COT - RSME - Mechanical Final |
|
Passed |
|