Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof NailingĀ 

Date Description Inspector Results Comments
08/12/2026 COT - RSBU - Roof NailingĀ  Re-inspection required 8-12-26: provide truss calcs, add anchor bolts to marked locations & tighten all loose anchors, missing AC6 Post cap at front porch column-remove section of osb at column to verify anchor bolts, add nails to sheathing along east side at marked areas, provide ladder to inspect roof.
Note: interior framing not inspected at contractors request & provide clarification on which west garage wall okay to be 2x4's.