Inspection Status: Re-inspection required

Inspection History: COT - BULD - SWG Clearance

Date Description Inspector Results Comments
05/19/2026 COT - BULD - SWG Clearance Re-inspection required 5-19-26: install pressure relief valve together a water heater pan.
05/21/2026 COT - BULD - SWG Clearance Re-inspection required 5-21-26: Per the International Residential Code (IRC) Section P2801, a water heater pan is required when a tank-type water heater is installed in a location where leaks could cause damage (e.g., attics, finished floors, or over living spaces). The pan must be at least 1.5 inches deep, made of corrosion-resistant material, and drained by a minimum 3/4-inch pipe. Additionally, the pressure relief valve cannot be threaded. Make corrections and reschedule inspection.
05/28/2026 COT - BULD - SWG Clearance Passed 5-28-26: okay to restore gas service. SWG clearance issued on meter pack- no serial number.