Inspection Status: Re-inspection required
Inspection History: COT - BULD - SWG Clearance
| Date |
Description |
Inspector |
Results |
Comments |
| 05/19/2026 |
COT - BULD - SWG Clearance |
|
Re-inspection required |
5-19-26: install pressure relief valve together a water heater pan. |
| 05/21/2026 |
COT - BULD - SWG Clearance |
|
Re-inspection required |
5-21-26: Per the International Residential Code (IRC) Section P2801, a water heater pan is required when a tank-type water heater is installed in a location where leaks could cause damage (e.g., attics, finished floors, or over living spaces). The pan must be at least 1.5 inches deep, made of corrosion-resistant material, and drained by a minimum 3/4-inch pipe. Additionally, the pressure relief valve cannot be threaded. Make corrections and reschedule inspection. |
| 05/28/2026 |
COT - BULD - SWG Clearance |
|
Passed |
5-28-26: okay to restore gas service. SWG clearance issued on meter pack- no serial number. |