| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2025 | BULD - Electrical Clearance | Passed | 6.23.25 Proper bonding and grounding verified, neutrals marked with white tape. Mast is sub 3ft no further bracing required. Ground rods 6ft apart. Water bonded, not gas at unit no gas bond req. Lugs torqued to spec with marks. Panel is properly secured. Clear to cut over. |