Inspection History Details
Inspection Status: Passed
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/14/2026 | RSBU - Building Final | Passed | ||
| 12/16/2025 | RSBU - Building Final | Re-inspection required | 12/16/25 1. Missing carbon monoxide detector; and per R315.6 should receive primary power from building wiring. 2. Smoke detectors are not UL listed and are not interconnected. May use UL listed Wireless smoke detectors per R314.4. 3. Range is missing anti-tip bracket. 4. Dishwasher is missing water hammer arrestor. 5. Ice maker missing water hammer arrestor. 6. Main panel schedule missing 7. Garage entry door needs to be solid core and self closing. 8. Breakers need to be ARC faulted rated for living rooms, bedrooms, dens and similar areas. |