Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof NailingĀ
| Date |
Description |
Inspector |
Results |
Comments |
| 08/12/2025 |
COT - RSBU - Roof NailingĀ |
|
Re-inspection required |
Shot pins and anchor bolt at marked areas, check edge spacing on sheathing at roof and walls, should be 6"oc, over penetration at wall sheathing throughout |
| 08/14/2025 |
COT - RSBU - Roof NailingĀ |
|
Passed |
See previous notes, h25 clips at sil plate not nailed properly/missing nails, sil plate at marked area west wall needed anchor bolt, not shot pin |