Inspection Status: Not Ready
Inspection History: RSBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 07/02/2026 |
RSBU - Building Final |
|
Not Ready |
Provide WR receptacles at all outdoor locations. Provide hammer arrestor for dishwasher hot line. Provide GFCI receptacles at laundry room area. Provide 220 outlet for dryer. Provide arc fault breakers at all living areas. Complete panel schedule. Secure condenser unit to pad. Secure seal tight whip. Water heater incomplete. 7/2/2026 |
| 07/10/2026 |
RSBU - Building Final |
|
Passed |
|