Inspection History Details
Inspection Status: Partial Pass
Inspection History: Pool/Spa - Plumbing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2026 | Pool/Spa - Plumbing | Partial Pass | Why is there a gas line in the trench? | |
| 05/29/2026 | Pool/Spa - Plumbing | Re-inspection required | 5/29/26 1. Gas line, pool, water and electrical conduit are all in the same trench. Gas line appears to be for a barbecue and has been valved off . Scotch guard has been scraped off the gas line due to the trenching. If gas line is abandoned then it will need to be removed from the gas meter and vented and capped off properly. furthermore if gas line is still active, it will need to be separated from electrical conduit by 12 inches horizontally. |
|
| 06/23/2026 | Pool/Spa - Plumbing | Re-inspection required | previous issue not addressed, will need proof of correction or have trench re dug. checked all alarm and safety devices, grounding, and electrical, all are correct | |
| 06/26/2026 | Pool/Spa - Plumbing | Canceled | ||
| 06/30/2026 | Pool/Spa - Plumbing | Passed | Correction made |