Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 04/22/2026 |
RSBU - Building Final |
|
Re-inspection required |
new flooring being installed at time of inspection. cannot get to all fixtures and plumbing lines to conduct inspection. 4/22/2026 |
| 04/24/2026 |
RSBU - Building Final |
|
Re-inspection required |
all water lines that are not within the thermal envelope requires insulation. hot water line that runs parallel to cold line requires insulation. access to crawl space is required. provide hammer arrestors where quick closing valves are installed. 4/24/2026 |
| 04/30/2026 |
RSBU - Building Final |
|
Passed |
All corrections were made. 4/30/2026 |