Permit: TC-RES-0326-01414

Parcel: 133477010

Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
05/07/2026 COT - RSME - Mechanical Final  Re-inspection required 1-Install locking caps on compressors.
2-5 Ton unit has undersized wires.
3-3-Ton unit is overfused.
05/15/2026 COT - RSME - Mechanical Final  Re-inspection required 3 ton unit is still over amped at fuse
Unit calls for minimum 29 and maximum 40, current amp breaker is 60 and so is overamped
05/26/2026 COT - RSME - Mechanical Final  Passed