Inspection Status: Passed

Inspection History: COT - RSEL - Electrical Underground 

Date Description Inspector Results Comments
05/13/2026 COT - RSEL - Electrical Underground  Passed 5/13/2026
2.5" schedule 40 conduit 15’ run from transformer to new ADU panel - okay to backfill with shading. 2" schedule 40 conduit run of 60’ from existing house new load center to new ADU panel - okay to backfill, shading required.