Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2026 | RSBU - Building Final | Re-inspection required | 5/14/2026 Changer breakers in habitat areas to AFCI, cover outlets in kitchen, hose missing in bathroom, missing kitchen sink, conduit and whip from AC unit needs blocks 3.5" from roof, AC needs breaker at 30A - currently is overamped at 60A. Add anti siphon device at hose bibb. |
|
| 05/15/2026 | RSBU - Building Final | Passed | 5/15/2026 Verified per approved plan all prior completed work. All corrections made to prior inspection. |