Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
02/12/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 2-12-26: missing restroom backing for toilet/shower-bathtub-see City of Tucson inclusive home page for details, anchor bolts are required within 12" at the end of each plate and spaced 4' apart thereafter, 2 anchor bolts are required within 12" on each side of a splice, missing nails at H25'S, missing H25 at south side - area marked in red, missing gable end bracing, provide truss calculations, unable to determine spacing along edges at 4" o.c. At smart side 190 siding, plans call for 2x6" top & bottom plates. Either submit a revision showing 2x4"s or install per plans. STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE ADDED.
02/18/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 2.18.26
Multiple items from previous list have not been addressed - inspection stopped.
02/19/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required (with fee) 2-19-26: add anchor bolts to marked locations and backing behind toilet between 33-36" aff.
02/20/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 2-20-26: exterior clips/sheathing approved. Okay to continue with construction.