Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 11/19/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
A2 and A1 trusses are in the wrong spot. Rfi on these trusses approval in field. Nailing pattern at exterior sheathing not per schedule. Add blocking to perimeter for proper nailing. Add shot pins to interior walls along with anchor bolts at exterior marked locations. Add cs16 strap at exterior north wall along at beams to post. Provide ladder for roof nailing inspection. 11/19/2024 |
| 12/30/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
12/30/24: All items noted on the 11/19/24 inspection have been corrected and are complete. Okay to proceed with further work. |