Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
11/19/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required A2 and A1 trusses are in the wrong spot. Rfi on these trusses approval in field. Nailing pattern at exterior sheathing not per schedule. Add blocking to perimeter for proper nailing. Add shot pins to interior walls along with anchor bolts at exterior marked locations. Add cs16 strap at exterior north wall along at beams to post. Provide ladder for roof nailing inspection. 11/19/2024
12/30/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 12/30/24: All items noted on the 11/19/24 inspection have been corrected and are complete. Okay to proceed with further work.