Inspection Status: Canceled
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2025 | RSBU - Building Final | Canceled | 6/23/25 Canceled |
|
| 06/25/2025 | RSBU - Building Final | Canceled | ||
| 07/01/2025 | RSBU - Building Final | Re-inspection required | 7/1/25 1. Receptacle in bathroom is not resetting. 2. Receptacle in kitchen under sink must be GFCI protected. 3. T-stat too high must be no higher than 48". 4. Outdoor receptacles must be "WR" stamped and tamper resistant 5. No access to HVAC unit, could not inspect. 6. No power at laundry receptacle 7. Threshold is too high must be no higher than 1/2" it is currently at 3.5". Please read cover page of your plan titled "Pima County Inclusive Home design for reference. |
|
| 07/14/2025 | RSBU - Building Final | Canceled | ||
| 07/15/2025 | RSBU - Building Final | Passed |