Parcel: 11921023A


Addresses:

3003 S MISSION RD


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Permit Number - TC-RES-0323-04011

Inspection Description - COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
01/09/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 01/09/25

1. Main wires penetrating through 2 holes in west wall; should be no more than 3 wires per hole;
2. Missing staples throughout within 8" of outlets and gang boxes.
3. Pancake box in living room east side is overloaded.
4. Romex running underfloor is not permitted, must run UF type cable underground to wet locations.

5. DWV not under test.

6. Supports required throughout with flex ducts.

7. Clean outs missing throughout.

8. Overnotched stud on north wall, requires stud shoe.
01/15/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed 01/15/25
Passed. All corrections have been made.