Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 09/11/2023 |
RSBU - Building Final |
|
Re-inspection required |
9/11/23 Need reciprocal (outlet) bedroom 1 needs to have receptacle within 6 ft, one kitchen receptacle no electrical power. Kitchen needs outlet next to stovetop counter within 2 ft. Panel not labeled. |
| 09/12/2023 |
RSBU - Building Final |
|
Re-inspection required |
Called left a voicemail and received no answer at the door. Need access to the site. 9/12/2023 |
| 09/14/2023 |
RSBU - Building Final |
|
Re-inspection required |
9/14/23: all kitchen countertop reciprocals need to be GFCI protected, food compose and dishwasher reciprocal needs to be GFCI protected, smoke detectors not hard wired or interconnected, outlet at laundry room needs to be GFCI protected STOPPED INSPECTION |
| 09/21/2023 |
RSBU - Building Final |
|
Passed |
|