Permit: TC-RES-0323-03579

Parcel: 113040760


Addresses:

1034 E PRINCE RD

Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Date Description Inspector Results Comments
09/11/2023 RSBU - Building Final  Re-inspection required 9/11/23 Need reciprocal (outlet) bedroom 1 needs to have receptacle within 6 ft, one kitchen receptacle no electrical power. Kitchen needs outlet next to stovetop counter within 2 ft. Panel not labeled.
09/12/2023 RSBU - Building Final  Re-inspection required Called left a voicemail and received no answer at the door. Need access to the site. 9/12/2023
09/14/2023 RSBU - Building Final  Re-inspection required 9/14/23: all kitchen countertop reciprocals need to be GFCI protected, food compose and dishwasher reciprocal needs to be GFCI protected, smoke detectors not hard wired or interconnected, outlet at laundry room needs to be GFCI protected STOPPED INSPECTION
09/21/2023 RSBU - Building Final  Passed