04/05/2024 RSBU - Building Final  Canceled
04/09/2024 RSBU - Building Final  Re-inspection required 4/9/24: Outdoor receptacles must be WR, properly brace riser at sub-panel, arc-fault breaker's missing at multiple locations at panel, properly label panel schedule, exterior plastic piping must be coated for UV protection, GFCI required under kitchen sink for disposal, water hammer arrestor missing at dishwasher, properly secure electrical whip at A/C unit and at water heater, hose bib needs to be insulated and wrapped with UV tape. Per Code E3604.2.1 conductors shall have a vertical clearance of not less then 8ft . MORE ITEMS MAY BE ADDED.
04/12/2024 RSBU - Building Final  Passed 4/12/24: Contractor has corrected items in above comments. Everything is good. Okay to issue Certificate of Occupancy for ADU.