Permit: TC-RES-0225-00876

Parcel: 137081230


Addresses:

301 W MELRIDGE ST

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
08/25/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 8-25-25: nailing at exterior sheathing not per plan-check spacing;plans call for 6" o.c. Along edges/joints and 12" o.c. In the field. Nailing can be no closer than 3/8" from edges and nails cannot overpenetrated more than 1/16". Add anchor bolts together with shot pins at marked locations and sill plates must be pressure treated. Add Simpson BC6 & Simpson ABA66 at all interior 3 posts to beams.
08/27/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed Approved. All corrections were made. 8/27/2025