Permit: TC-RES-0225-00876

Parcel: 137081230


Addresses:

301 W MELRIDGE ST

Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Date Description Inspector Results Comments
06/03/2026 RSBU - Building Final  Re-inspection required 6-3-26: arch fault breakers/gfci's at kitchen receptacles are required, install hammer arrestor at dishwasher, install anti-tip device at stove, install 4" address numbers on home, missing sediment trap at gas water heater, install pressure relief valve at water heater, install hose bib and vacuum breaker, missing knockouts at panel, label breakers, install arch fault breakers/gfci's for habitable areas to include, kitchen and bedroom, exterior receptacles must be weather resistant gfci's, gfci receptacles are required at laundry room, missing concrete landings at sliding glass door & kitchen door, paint all exterior plastic at rooftop, missing shower tempered glass door, provide ladder for roof access, properly loop dishwasher lines. Schedule inspection for new porch- this was never inspected, Stopped inspection additional items may be noted.
06/12/2026 RSBU - Building Final  Passed 06/12/2026
Corrections made to prior inspection, verified rest of addition and rear patio.