Permit: TC-RES-0225-00785

Parcel: 137060550


Addresses:

533 W DAKOTA ST

Inspection Status: Passed

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
05/28/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 5/28/2026
Passed on prior inspections, verified corrections made.
10/27/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 10-27-25: add an anchor to marked location at garage-anchor bolts are required within 12" at the end of each plate. Add shot pin within 6" at the end of plate and space 24" o.c., nailing for exterior not per plan-add nails along edges/joints no closer than 3/8" from joints and 12" o.c. In the field. Add nails to sheathing where nails over penetrate more than 1/8". Missing A35's and H25's at ledger at back exit to patio, add 2x6 blocking at 6' apart for gable end truss, add anchor bolts to all sides of columns and add studs per plans, missing Simpson nail plates to top plates at 48" o.c.-see plans for details.STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE ADDED.