Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
07/14/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 7-14-25: Add anchor bolts 23" throughout-see details A-301#3&1. Add shot pins to marked areas-shot pins re required 6" from the end of an interior plate, several loose roof panels-add nails t marked locations, and a CS16 straps on interior posts to beam with 8 nails above and below connecting points.Submit a revision for all perimeter framing gaps along existing masonry walls, add nails to exterior sheathing at entry way where nails along edges/joints are closer than 3/8" and where overpenetrated more than 1/16".
07/21/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 7-21-25: exterior clips/sheathing approved. Okay to continue with construction.
Note: add firefoam along interior framing at ceiling/rooftop gaps-this will be verified at intermediates.