Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof NailingĀ
| Date |
Description |
Inspector |
Results |
Comments |
| 06/04/2025 |
COT - RSBU - Roof NailingĀ |
|
Re-inspection required |
6/4/25: Fastners shall penetrate no more than 1/8" and shall be no closer than 3/8" from edge of sheathing. Spacing at sheathing not per plan at north west corner of home (marked in red), shot pins required 6" from edge of sill plate, truss clacs must be provided at time of inspection, 2x4 at nailer truss must be spaced 24" o.c, |
| 06/06/2025 |
COT - RSBU - Roof NailingĀ |
|
Passed |
Approved. All items have been completed. 6/6/2025 |