Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
04/18/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Loose shear panels. Proved titan bolts at all that are out of the center third of the bottom plates. Add cut nails to interior walls along with fire blocking at 8ยด.
04/22/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 4/22/24: Loose shear panels have been properly nailed off, bolts have been drilled into plate and floor on bottom plate, cut nails have been added to bottom plate on interior walls and fire blocking is installed at 8' height in all walls.