Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
05/23/2025 COT - RSME - Mechanical Final  Re-inspection required 5/23/25
1. Garbage disposal/dishwasher needs to be on GFCI,
2. Water hammer arrestors needed at dishwasher.
3. GFCI needed at laundry
4. Sub panel is in closet, and does not meet code.
5. Water heater, t/p line is missing.
6. Thermostat too high. 48" Max
7. Exterior outlets need to be WR/TR rated.
8. Condensate line needs to be painted to prevent UV damage
9. HVAC Max fuse is 40 amps, you have a 60A fuses in there.
10. HVAC service outlet needs to WR rated.
06/10/2025 COT - RSME - Mechanical Final  Passed