Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date |
Description |
Inspector |
Results |
Comments |
| 02/15/2024 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Re-inspection required |
1-Feeders for sub-panel are not in conduit. 2-Secure oven conductors at sub-panel. 3-Install exterior switch controlled lighting. 4-Provide an emergency escape and rescue opening for Master Bedroom per Code. |
| 02/20/2024 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Re-inspection required |
1-Secure wires within 8" of box, or provide clamp. 2-Provide bushing/clamps at metal boxes. 3-Ground metal boxes. 4-Feeder for sub-panel is still not in conduit. |
| 02/22/2024 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Re-inspection required |
corrections not completed. |
| 02/26/2024 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Passed |
2/26/24: Wires have been secured within 8" of boxes, all metal boxes have romex connectors at wire entrance and ground wire is secured to grounding screw in box, conduit has been added from wall to subpanel for feeder wire. Okay to insulate and drywall walls and ceiling. |