Permit: TC-RES-0123-02003

Parcel: 130103170


Addresses:

3257 E 30TH ST

Inspection Status: Not Ready

Inspection History: COT - RSPL - Plumbing Final 

Date Description Inspector Results Comments
10/19/2026 COT - RSPL - Plumbing Final  Not Ready Properly label panel due to miss labeled. Provide WR receptacles at all outdoor locations. Complete tie in at dryer. Provide GFCI receptacle for washer. Outdoor receptacle all tied into same circuit as inside. Both outdoor shall be dedicated. Provide a dedicated circuit for mini split circuit. Per manufacturer specifications. Screw disconnect box due to loose lid. Extend condensation line and secure to wall. Secure mini split to pad. Properly provide protection to line sets and seal off penetration. Provide clamp within 12” from disconnect. Provide vacuum breaker at hose bib. Ensure door handle meet ada requirements along with threshold. 10/19/2026