Inspection Status: Partial Pass
Inspection History: RSBU - Building Progress
Permit Number - TC-RES-0123-01910
Inspection Description - RSBU - Building Progress
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/05/2023 | RSBU - Building Progress | Partial Pass | Partial pass. looked at three trusses that have been sistered above the front bedroom with 2x6’s. plans ask for 2x8’s need to be submitted for revision. proceed at own risk. 7/5/2023 | |
09/01/2023 | RSBU - Building Progress | Passed | 9/1/23: framing is good in addition to the west of main entry | |
10/26/2023 | RSBU - Building Progress | Canceled | Canceled per contractor. 10/26/23 | |
10/31/2023 | RSBU - Building Progress | Re-inspection required | 10/31/23: support 4-gang box at entrance, seal penetrations through top plate, missing receptacles at kitchen (disposal switch, counter top), receptacle box missing at kitchen countertop, verify location of sub-panel, thermostat must be mounted no more than 54" above finish floor, bathroom exhaust fans not terminating through the roof, blocking required on 3 sides of A/C registers (missing in guest house),ground all metal boxes, DWV not under test. | |
11/13/2023 | RSBU - Building Progress | Passed |