Inspection History: COT - BULD - SWG Clearance

Date Description Inspector Results Comments
07/05/2023 COT - BULD - SWG Clearance Canceled Canceled per contractor. 7/5/2023
10/26/2023 COT - BULD - SWG Clearance Canceled Canceled per contractor. 10/26/23
10/31/2023 COT - BULD - SWG Clearance Re-inspection required 10/31/23: support 4-gang box at entrance, seal penetrations through top plate, missing receptacles at kitchen (disposal switch, counter top), receptacle box missing at kitchen countertop, verify location of sub-panel, thermostat must be mounted no more than 54" above finish floor, bathroom exhaust fans not terminating through the roof, blocking required on 3 sides of A/C registers (missing in guest house),ground all metal boxes, DWV not under test.
11/13/2023 COT - BULD - SWG Clearance Passed Canceled per contractor. 7/5/2023

Canceled per contractor. 10/26/23
10/31/23: support 4-gang box at entrance, seal penetrations through top plate, missing receptacles at kitchen (disposal switch, counter top), receptacle box missing at kitchen countertop, verify location of sub-panel, thermostat must be mounted no more than 54" above finish floor, bathroom exhaust fans not terminating through the roof, blocking required on 3 sides of A/C registers (missing in guest house),ground all metal boxes, DWV not under test.

11/13/23: SWG Clearance