Permit: TC-MDP-1224-01390

Parcel: 141450390


Addresses:

6490 E PASEO ALGA

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
09/02/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9.2.2025
Missing 6” screws on floor trusses in first floor per truss calcs, missing A35 clips on detail SD2-14, missing H2.5 or mechanical connection clips on second floor at JG1 & JG2 trusses (see red markings), nail loose sheathing per red markings on second floor and bottoms plates.
09/05/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 9.52025
Corrections made from prior inspection, verified with letter that mechanical connection on roof girder truss at JG1 to B1G is correct with heel and nails.