Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
Permit Number - TC-MDP-1223-01899
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2024 | COT - RSEL - Electrical Final | Re-inspection required | 8/22/24: missing bushing at knockout, properly secure electrical whip at A/C condenser, secure clean out cap at cleanouts, exterior framing must be coated, replace or clean rated door tag at garage door, hammer arrestor must be cleaned to view listing, clean out missing at kitchen sink, AVV must be above flood level. Clearance at b-vent not meeting code at attic. | |
08/26/2024 | COT - RSEL - Electrical Final | Re-inspection required | missing bushing at knockout, clean out missing at kitchen sink, AVV must be above flood level, hammer arrestor must be cleaned to view listing. 8/26/2024 | |
08/27/2024 | COT - RSEL - Electrical Final | Passed | 8/27/2024 corrections have been made |