Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 10/22/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
10-22-25: SW2 at garage & on other side of staircase calls for anchor bolts 32" o.c. Or Ramset pins at 8" o.c., missing sheathing at shear walls, missing fire blocking at staircase, add a shot pin within 6" at the ends of sill plate, add angle clips to every other stud at upstairs firewall, add nails and 2x4 to damaged sill plate to decking at upstairs southeast bedroom, missing A-35's and at each end of garage and at garage shear wall at 16" o.c., add nails at edge underneath front porch, missing A-34’s at each end of gable end bracing. |
| 11/03/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Canceled |
11-3-25: canceled by contractor. |
| 11/05/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
11-5-25: corrections made-exterior clips/sheathing and framing approved. |