Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 07/02/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Add a 35 clips above shear wall in garage per intermediate. Add h25 at heel truss. Add anchor bolts at marked areas. Missing pins at interior. 6" from edges at 24" o.c. Add nails and rsps south wall. 7/2/2025 |
| 07/07/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
7-7-25: missing RSP4 top/bottom together with nails on another rsp4 on southside, add shot pins to marked locations, and an anchor bolt at north side of garage. |
|
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required (with fee) |
7-9-25: missing nails to rsp4 located on southside-stud is marked in red, and add nails to A-35'svat garage shear wall. |
| 07/10/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
7-10-25: exterior clips/sheathing approved. Okay to continue with construction |