Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
07/22/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 7-22-25: install longer coil strap as Detail SD3-12B calls for 8 nails above/below interconnecting points from post to beam on exterior side, missing nails to RSP4 located on north side, add 2 anchor bolts to marked locations on south side of home, exterior sheathing at garage calls for 4" o.c. and 12" in the field-add nails per schedule and where nails over-penetrate more than 1/16", add shot pins to marked locations, add H-25's to trusses CG48C, missing gable wall & truss bracing at back patio outlined per Detail SD3-7, loose roof panel at great room, missing A-35's at garage drag truss per Detail 6A-SD3.
07/24/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 7.24.25
Some corrections made. Remaining items are as follows:
Coil strap at back patio per SD3 - 12b
Gable wall truss bracing per SD3-7
07/24/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 7/25/25
Pass