Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof NailingĀ 

Date Description Inspector Results Comments
07/22/2025 COT - RSBU - Roof NailingĀ  Re-inspection required 7-22-25: install longer coil strap as Detail SD3-12B calls for 8 nails above/below interconnecting points from post to beam on exterior side, missing nails to RSP4 located on north side, add 2 anchor bolts to marked locations on south side of home, exterior sheathing at garage calls for 4" o.c. and 12" in the field-add nails per schedule and where nails over-penetrate more than 1/16", add shot pins to marked locations, add H-25's to trusses CG48C, missing gable wall & truss bracing at back patio outlined per Detail SD3-7, loose roof panel at great room, missing A-35's at garage drag truss per Detail 6A-SD3.
07/24/2025 COT - RSBU - Roof NailingĀ  Passed 7.24.25
Roof sheathing satisfactory