Permit: TC-MDP-1123-01792

Parcel: 11808081B


Addresses:

972 W SILVERLAKE RD

Inspection Status: Not Ready

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
04/12/2024 COT - RSME - Mechanical Final  Not Ready
04/18/2024 COT - RSME - Mechanical Final  Re-inspection required 4/18/24: weep screed clearance must be 4" above grade (not meeting clearance throughout), water heater T&P drain must terminate 6" above grade, water heaters missing pan per code P2801.6 and pan shall drain no less than 6" above grade, A/C condensate drain must be UV coated, Arc-fault breakers required at kitchen circuits and laundry circuit. Cut clean outs to grade.
04/19/2024 COT - RSME - Mechanical Final  Passed 4/18/24: weep screed clearance must be 4" above grade (not meeting clearance throughout), water heater T&P drain must terminate 6" above grade, water heaters missing pan per code P2801.6 and pan shall drain no less than 6" above grade, A/C condensate drain must be UV coated, Arc-fault breakers required at kitchen circuits and laundry circuit. Cut clean outs to grade.
4/19/24: corrections made.