Permit: TC-MDP-1025-00695

Parcel: 140445380


Addresses:

6037 E GABILAN LN

Inspection Status: Not Ready

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
03/03/2026 COT - RSEL - Electrical Final  Not Ready 03/03/2026
Not ready.
03/11/2026 COT - RSEL - Electrical Final  Re-inspection required 3/11/2026
AC breaker overamped 50A at main panel - manufacturer label calls for max 40A breaker, mini-split unit outside needs to be secured to pad, no ladder provided upstairs to verify attic equipment.
03/20/2026 COT - RSEL - Electrical Final  Passed 3/20/2026
All corrections are to prior inspection.