Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-MDP-1025-00695

Parcel: 140445380


Addresses:

6037 E GABILAN LN

Inspection Status: Not Ready

Inspection History: RSBU - Building Final 

Date Description Inspector Results Comments
03/03/2026 RSBU - Building Final  Not Ready 03/03/2026
Not ready.
03/11/2026 RSBU - Building Final  Re-inspection required 3/11/2026
AC breaker overamped 50A at main panel - manufacturer label calls for max 40A breaker, mini-split unit outside needs to be secured to pad, no ladder provided upstairs to verify attic equipment.
03/20/2026 RSBU - Building Final  Passed 3/20/2026
All corrections are to prior inspection.