Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - RSME - Mechanical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2026 | COT - RSME - Mechanical Final | Not Ready | 03/03/2026 Not ready. |
|
| 03/11/2026 | COT - RSME - Mechanical Final | Re-inspection required | 3/11/2026 AC breaker overamped 50A at main panel - manufacturer label calls for max 40A breaker, mini-split unit outside needs to be secured to pad, no ladder provided upstairs to verify attic equipment. |
|
| 03/20/2026 | COT - RSME - Mechanical Final | Passed | 3/20/2026 All corrections are to prior inspection. |