Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2026 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | 06/29/2026 Fire caulk top plate penetrations throughout, add steel nail plates as marked to 8AWG wire within 1.25" to stud face and tape torn sheathing in garage, add stud shoes to over-notched 2x6 in laundry room, move eletrical receptacle in bedroom within 6’ of door measured along floor line of wall. |
|
| 06/30/2026 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required (with fee) | 6/30/26: Sewer line damaged. Rescheduled inspection once repair is made. Pressure test required. Damaged sheathing at EV has to be repaired, properly insulate water lines in unconditioned space, over notched studs at laundry room have not been addressed, nail plates required in laundry room and bedrooms, h2.5 at bedroom south needs nails, make up wires at master bedroom receptacle. | |
| 07/02/2026 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed |