Permit: TC-MDP-1025-00610

Parcel: 140281210

Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
09/15/2026 COT - RSEL - Electrical Final  Re-inspection required 9-15-26 EV charger at garage needs to be EVSE or WTPE shall be listed *both smoke detectors Hallway are required to be within 12 inches from wall. * properly label circuit 28 in main panel.* add a strap for irrigation whip to panel * ensure 3 inch clearance around condensation pad mainly to the west.
09/18/2026 COT - RSEL - Electrical Final  Passed 9-18-26 All previous items have been corrected electrical final approved