Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Interior Shear BracingĀ 

Date Description Inspector Results Comments
10/27/2025 COT - RSBU - Interior Shear BracingĀ  Re-inspection required 10-27-25: per table R702.3.5 of the 2018 IRC nails for 1/2" drywall at non shear walls can be spaced along edges no greater than 8" o.c... add nails along the base throughout on both levels and schedule a reinspected when ready.
10/28/2025 COT - RSBU - Interior Shear BracingĀ  Passed 10.28.2025
Corrections made from yesterday's inspection.