Parcel: 140442840


Addresses:

6105 E CAMPOLINA TR


Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Permit Number - TC-MDP-1024-01218

Inspection Description - COT - RSME - Mechanical Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
05/01/2025 COT - RSME - Mechanical Final  Re-inspection required 5/1/25: All exterior plastic piping must be coated for UV protection, A/C condensate drain was terminated using CPVC glue (primer and pvc glue required), Riser for Main panel is not secured to wall, door bell not installed, insulate and wrap refrigerant lines at a/c condenser, properly secure electrical whip at A/C disconnect, repair stucco, use appropriate fasteners for clamps at A/C disconnect, Noalax required at aluminum conductors at a/c disconnect, CPVC glue not allowed on PVC piping, thermostat shall be no higher than 48"o.c, A.A.V required at kitchen island, smoke detector missing outside upstairs bedrooms, B-vent for furnace has negative pitch, B-vent at air handler requires 3 fasteners (connection not made), supply in attic must be connected to plenum box. properly secure gas piping at furnace in attic. STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
05/16/2025 COT - RSME - Mechanical Final  Passed