Permit: TC-MDP-1024-01206

Parcel: 140443260


Addresses:

6102 E CAMPOLINA TR

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Date Description Inspector Results Comments
03/23/2026 COT - RSBU - Roof Nailing  Re-inspection required 3.23.26
Missing diagonal bracing at west end per detail 5-sd1.3b

Damaged metal bracing at trusses in multiple locations

Damaged vertical member at (x2) A2 truss requires engineer fix (toward middle of structure)

INSPECTION STOPPED - MORE ITEMS MAY BE PRESENT
03/27/2026 COT - RSBU - Roof Nailing  Re-inspection required 3.27.26
Truss marked on floor with red marker

Roof has been papered and battens applied before inspection. Provide and submit letter of responsibility and liability from builder or permit entity for roof nailing.
04/07/2026 COT - RSBU - Roof Nailing  Passed 04/07/2026
Corrections made to prior inspections and detailed engineer fix/letter verified.