Permit: TC-MDP-1024-01203

Parcel: 140062760


Addresses:

3609 E NEBRASKA SV

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Preslab  

Date Description Inspector Results Comments
05/08/2025 COT - RSBU - Preslab   Re-inspection required 5/8/25: Address required on site, Site plan required on site, reinforcement overlap must be 24" min, all reinforcement must maintain 3" from grade, A.B required at slab to tamped down, Footing size not per plan. all plastic piping that will be in contact with concrete must be fully wrapped.
05/13/2025 COT - RSBU - Preslab   Passed 5/13/25
All corrections are made.