Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof NailingĀ
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2025 | COT - RSBU - Roof NailingĀ | Re-inspection required | 7-21-25: add shot pins within 6" at the end of plate and 24" o.c. Thereafter, missing nails to RSP4 on south side, missing RSP4 on north & south ends of home, add nails to A-35's throughout, missing A-35's at south end of garage,south of kitchen island, back patio, and at north & south end of home, missing nails at garage shear panel-plans call for 6" o.c. at edges/joints, missing nails at exterior sheathing at garage-4" o.c., missing H-25 at truss CG48C, loose roof panels at southeast are of garage and at back patio, provide truss calculations, STOPPED INSPECTION-ADDITIONAL ITEMS MSY BE ADDED. | |
| 07/23/2025 | COT - RSBU - Roof NailingĀ | Passed | 7-21-25: add shot pins within 6" at the end of plate and 24" o.c. Thereafter, missing nails to RSP4 on south side, missing RSP4 on north & south ends of home, add nails to A-35's throughout, missing A-35's at south end of garage,south of kitchen island, back patio, and at north & south end of home, missing nails at garage shear panel-plans call for 6" o.c. at edges/joints, missing nails at exterior sheathing at garage-4" o.c., missing H-25 at truss CG48C, loose roof panels at southeast are of garage and at back patio, provide truss calculations, STOPPED INSPECTION-ADDITIONAL ITEMS MSY BE ADDED. 7.23.25 Satisfactory corrections made, no additional items found. |