Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
05/29/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 5/29/25: Anchor bolts required with 12" of edge of sill plate, shear walls not fastened per schedule, fasteners shall be no closer than 3/8" from edge and shall penetrate no more than 1/8", incorrect hangers used at truss EJ41 (plans call for LSU24), Anchor bolts required at front porch columns and back porch columns, Gabel end bracing required at back porch framing, gabel end bracing missing throughout, Gabel end bracing spacing at garage not per plans, H2.5 required at truss A41B (2). STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
06/02/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 6-2-25: no plans on site. Arrived on site at approximately 6:50, contacted contractor at 7:04 and left at 7:23
06/03/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 6-3-25: exterior clips/sheathing approved. Okay to continue with construction.