Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Date Description Inspector Results Comments
05/29/2025 COT - RSBU - Roof Nailing  Re-inspection required 5/29/25: Anchor bolts required with 12" of edge of sill plate, shear walls not fastened per schedule, fasteners shall be no closer than 3/8" from edge and shall penetrate no more than 1/8", incorrect hangers used at truss EJ41 (plans call for LSU24), Anchor bolts required at front porch columns and back porch columns, Gabel end bracing required at back porch framing, gabel end bracing missing throughout, Gabel end bracing spacing at garage not per plans, H2.5 required at truss A41B (2). STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
06/02/2025 COT - RSBU - Roof Nailing  Re-inspection required 6-2-25: no plans on site. Arrived on site at approximately 6:50, contacted contractor at 7:04 and left at 7:23
06/03/2025 COT - RSBU - Roof Nailing  Passed 6-3-25: roof nailing approved.